Overview

The MPQ2000 portable power quality analyser has features which make it ideal for testing power quality in any environment, including rugged, weatherproof hardware, and the ability to power off Phase A or auxiliary power.

Features
- Power off Phase A or auxiliary, allowing it to be used anywhere Weather proof to NEMA 4 standard for use in any environment
- Auto CT identifies the current that the instrument is connected to and the range that it is in
- Configuration verification which highlights if the product has been connected incorrectly
- On-board data analysis which can compare results against compliance standards, including setting templates for internal company standards

Keywords
NA
Electrical Specifications
- Input Power :Phase A 90-600V 50Hz/60Hz or 105-600V DC or Aux Input Power - 120/240 V, 50/60 H
- Water-tight cord to operate off standard US, UK and EU plugs
- Supports live connect/disconnect
- Battery: NiMH battery pack (field replaceable)
- Discharge time – 8 hours
- Recharge time – 3 hours
- Data storage:External SD card (up to 32 GB)
- Communication
Ethernet -communications: network communications. Wireless communications with off-the-shelf bridge.USB stick - transfer data file to USB. Transfer setup configurations to and from USB stick. Perform firmware upgrades using USB stick
- SD card: automatically writes data to SD card; no manual transfer required Transfer setup configurations to and from SD card. No tool needed to access the SD card
- Display: Backlit 11.5 cm x 8.5cm color VGA
- PQ Events Dips / sags: Triggers off of voltage and current. IEC61000-4-30 compliant
- Swells: Triggers off of voltage and current, IEC61000-4-30 Compliant
- Sub-cycle distortions: Triggers off of voltage and current. IEC61000-4-30 compliant
- Transient detection: 1 µsecond. Triggers off of first 3 voltage channels, IEC61000-4-30 compliant
- THD: Triggers off of voltage and current, IEC61000-4-30 Compliant
- Rapid Voltage Change (RVC): Triggers off of first 3 voltage channels, IEC61000-4-30 compliant
- Phase shifts: Trigger event when a phase shift occurs between the voltage channels. Record date and time, duration and waveforms of all enabled channels. Phase shift user selectable down to 1 degree
- Waveform capture of events: Capture waveforms on all enabled channels when an out of limits event occurs. Waveforms programmable with up to 9 pre-trigger cycles and 99 post-trigger cycles
- Timed waveform capture: Captures waveforms periodically on all enabled channels. Waveform capture interval programmable down to 1 cycle. Programmable number of cycles to be captured up to 99 cycles
- Event triggered waveforms and timed triggered waveforms simultaneously
- Mains signaling events: Two selectable frequencies and amplitudes
- Selectable time interval. Measured per IEC61000-4-30
- Captures waveforms on all enabled channels when a mains signaling event occurs. Waveform programmable with up to 9 pre-trigger cycles and 99 post-trigger cycles
- Event Flagging: Measured per IEC61000-4-30.Motor Inrush
- Records RMS, Power and PF at a 1 cycle resolution
- Capture inrush current during motor start up
- Support both three-phase and single-phase motors, Real Time Data
- Scope Mode: View waveforms in scope mode
- Resolution: 16 bit analog to digital converter on 8 channels
- Max sampling speed: 1 MHz max
- Max RMS sampling: 17,664 per channel max
- PLL synchronization: 42.5 Hz to 69 Hz
- Real Time Clock Accuracy: ±20 ppm
- Voltage 4 voltage channels (isolated)
- Voltage range: 0 to 1000 V range AC RMS DC
- Measures AC & DC simultaneously (NO common neutral required)Voltage accuracy: 0.1% per IEC61000-4-30
- Voltage ratios: Adjustable voltage ratios for measuring secondaries. (.0001 through 9999)
- Resolution: 16 bit
- Crest factor: 1.5
- Max pk voltage: 1628 V / 2500 V
- Voltage lead set: 4 voltage leads, 6 ft (2 m) in length. Safety banana leads. Removable alligator clips. Optional plunger clips. Set of color bands for customizing color codes. Safety green/yellow ground lead included
- Fused adapter: In line with voltage leads to provide fuse
- Protection (optional)
- Current Channels; 5 current channels
- Current range: 0 to 6000 A (CT dependent)
- Current ratios:Adjustable current ratios for measuring secondaries (o through 9999)
- Current accuracy: ±0.5% of reading ±0.05% of full scale
- Resolution: 16 bit
- Crest factor: 4.0
- Power and Energy ;Active power (KW): Per IEEE1459
- Reactive power (KVAR): Per IEEE1459
- Apparent power (KVA): Per IEEE1459
- Energy parameters (KWH, KVARH, KVAH): Per IEEE1459
- Displacement power factor range: -1.0 to +1.0
- Displacement power factor accuracy: = ±0.02 + CT error
- True power factor range: 0.0 to +1.0
- True power factor accuracy: = ±0.02 + CT error
- Power configurations: 11Aggregation window: 1 cycle to 1 hour - fixed and sliding windows
- Unbalance: ANSI & IEC methodology per IEC61000-4-27
- Total Harmonic Distortion (THD): Per IEC61000-4-30 per IEC61000-4-7
- Harmonics: 0 through 50th continuous
- Inter-harmonics: 0 through 50th continuous
- Total Demand Distortion (TDD): Per IEEE519
- Frequency: Per IEC61000-4-30
- Flicker: Per IEC61000-4-15

General Specifications
- Environmental Operating: -20° C to 50° C (-4° F to 122° F)
- Storage: -30° C to 60° C (-22° F to +140° F)
- Relative humidity: 0-95% non-condensing
- Altitude <2000 m: 1000V CAT III / 600 V CAT IV
- Altitude 2000 m - 4000 m: 600 V CAT III / 300 V CAT IV
- Altitude 4000 m - 5000 m: 300 V CAT III / 150 V CAT IV
- Ruggedized enclosure IP54 when closed Lockable by means of padlock
- Dimensions: 305 mm x 266 mm x 143 mm (12.01 in. x 10.47 in. x 6.38 in Weight)
- Standard unit: 2.27 kg (5 lbs)

Brand SKU
NA

Rashi Part SKU
NA

Warranty
1 Year